Proper Flow is maintained through the heat source.
Heat Source can be set to desired temperature setting with no mixing required.
No minimum return fluid temperature is required for the heat source.
All the necessary conditions and piping practices, as outlined by the heat source manufacturer, are properly maintained.
Features
Full port ball valve
3/4” compression fitting
Function-optimized insulation design made of durable elastic EPP, 100% insulation of the fittings, ventilation openings to cool the pumps.
Free access to the pump head by simply pulling off the cover
Flow Check valve in return pipe prevents noise when electronically controlled pumps are used, low pressure drop, manual opener for faster line drain service, spring-actuated suited for horizontal, vertical or flow down assembly
Supply and return line can be changed on site.
All water-carrying parts are made of brass
All metal temperature gauges can be pulled off, integrated in the ball valve with an immersion sleeve
Pump can be replaced or serviced without draining the system.
Fully assembled with flat sealing union connections at most joints including 1" connection nut for the installation on PAW-distribution manifold. For standalone assembly, use the conversion kit with wall bracket from the PAW-assembly accessories.
The insulation of the distribution manifold is integrated in the insulation of the zone module.
Specifications
Dimension 3/4" Materials Fittings Brass Gasket EPDM/NBR Insulation EPP Technical Data Max. Pressure 116 Psi/8 Bar Max Temperature 230°F/110°C Cv Value 4.3 Dimensions Supply/Return line to Manifold 1" Male Supply/Return line to heating zone3/4" Compression Fitting Pre-Center Distance 90mm/3.5" Length255mm/10" Width Insulation180mm/7-1/16" Height Insulation385mm/15-1/8"
Recommended Application: High/Floating temperature zone control up to 56.7kBTU/h at dT=20°F